1. What is back siphonage?
Back siphonage is the reversal of normal flow in a system caused by a negative
pressure (vacuum or partial vacuum) in the supply piping.
2. What factors can cause back siphonage?
Back siphonage can be created when there is stoppage of the water supply due to
nearby fire fighting, repairs or breaks in city main, etc. The effect is similar to the
sipping of an ice cream soda by inhaling through a straw, which induces a flow in the
opposite direction.
3. What is backpressure ?
Backpressure is the reversal of normal flow in a system due to an increase in the
downstream or customer’s pressure above that of the supply pressure.
4. What factors can cause a backpressure condition?
Backpressure is created whenever the downstream pressure exceeds the supply
pressure, which is possible in installations such as heating systems, elevated
tanks, and pressure-producing systems. An example would be a hot water space heating boiler operating less than 15-20 lbs. Pressure coincidental with a reduction of
the city water supply below such pressure (or higher in most commercial boilers). As
water tends to flow in the direction of least resistance, a backpressure condition
would be created and the contaminated boiler water would flow into the potable water
supply.
5. What is a cross‐connection?
A cross-connection is a direct arrangement of a piping line which allows the potable
water supply to be connected to a line which contains a contaminant. An example is
the common garden hose attached to a sill cock with the end of the hose lying in a
cesspool. Other examples are a garden hose attached to a service sink with the end of
the hose submerged in a tub full of detergent, supply lines connected to bottom-fed
tanks, supply lines to boilers.
6. What is the most common form of a cross‐connection?
Ironically, the ordinary garden hose is the most common offender as it can be easily
connected to the potable water supply and used for a variety of potentially dangerous
applications.
7. What is potentially dangerous about an unprotected outside spigot or sill
cock?
The purpose of a sill cock is to permit easy attachment of a hose for outside watering
purposes. However, a garden hose can be extremely hazardous because they are left
submerged in swimming pools, lay in elevated locations (above the sill cock)
watering shrubs, chemical sprayers are attached to hoses for weed-killing,
etc.; and hoses are often left lying on the ground which may be contaminated with
fertilizer, cesspools, and garden chemicals.
8. What protection is required for sill cocks?
A hose bibb vacuum breaker should be installed on every sill cock to isolate garden
hose applications thus protecting the potable water supply from contamination.
Should a hose bibb vacuum breaker be used on frost-free hydrants? Definitely,
providing the device is equipped with means to permit the line to drain after the
hydrant is shut-off. A “removable” type hose bibb vacuum breaker could allow the
hydrant to be drained, but the possibility exists that users might fail to remove it for
draining purposes, thus defeating the benefit of the frost-proof hydrant feature. If the
device is of the “Non-Removable” type, be sure it is equipped with means to drain the
line to prevent winter freezing.
9. Can an atmospheric, anti‐siphon vacuum breaker be installed on a hose
bibb?
Theoretically yes, but practically no. An anti-siphon vacuum breaker must be
elevated above the sill cock to operate properly. This would require elevated piping
up to the vacuum breaker and down to the sill cock and is normally not a feasible
installation. On the other hand, a hose bibb vacuum breaker can be attached directly
to the sill cock, without plumbing changes and at minor cost.
10. What is an atmospheric vacuum breaker?
The most commonly used atmospheric anti-siphon vacuum breakers incorporate an
atmospheric vent in combination with a check valve. Its operation depends on a
supply of potable water to seal off the atmospheric vent, admitting the water to
downstream equipment. If a negative pressure develops in the supply line, the loss of
pressure permits the check valve to drop sealing the orifice while at the same time the
vent opens admitting air to the system to break the vacuum.
11. Will an anti‐siphon vacuum breaker protect against a backpressure
condition?
Absolutely not! If there were an increase in the downstream pressure over that of
the supply pressure, the check valve would tend to “modulate” thus permitting the
backflow of contaminated water to pass through the orifice into the potable water
supply line.
12. Can an atmospheric vacuum breaker be used on lawn sprinkler systems?
Yes, if these are properly installed, they will protect the potable water supply. The
device shall be installed 6" above the highest sprinkler head and shall have no control
valves located downstream from the device.
13. Can an atmospheric vacuum breaker be used under continuous pressure?
No! Codes do not permit this as the device could become “frozen”, and not function
under an emergency condition.
14. Can a pressure vacuum breaker be used on a multi‐zone lawn sprinkler
system?
Yes. This type of vacuum breaker can be used under continuous pressure. Therefore,
if properly installed, it will protect the potable water supply. The assembly shall be
installed 12" above the highest sprinkler head.
15. What is continuous pressure?
This is a term applied to an installation in which the pressure is being supplied
continuously to a backflow preventer for periods of over 12 hours at a time.
Laboratory faucet equipment, for example, is entirely suitable for a non-pressure,
atmospheric anti-siphon vacuum breaker because the supply is periodically being
turned on and shut off. A vacuum breaker should never be subjected to continuous
pressure unless it is of the continuous pressure type and clearly identified for this
service.
16. Are check valves approved for use on boiler feed lines?
Most jurisdictions require backflow protection on all boiler feed lines. Some will
allow a backflow preventer with intermediate vent as minimum protection for
residential boilers. A reduced pressure backflow preventer is generally required on
commercial and compound boilers. However, low cost, continuous pressure
backflow preventers are now available which will perform with maximum protection;
thus check valves are not recommended.
17. What is the difference between pollution and contamination?
Pollution of the water supply does not constitute an actual health hazard, although the
quality of the water is impaired with respect to taste, odor or utility. Contamination
of the water supply, however, does constitute an actual health hazard; the consumer
being subjected to potentially lethal water borne disease or illness.
18. What does “Degree of Hazard” mean?
The degree of hazard is a commonly used phrase utilized in cross-connection
programs and is simply a determination on whether the substance in the non-potable
system is toxic (health hazard) or non-toxic (non-health hazard).
19. What is the difference between a toxic and a non‐toxic substance?
Toxic substance is any liquid, solid or gas, which when introduced into the water
supply creates, or may create a danger to health and well being of the consumer. An
example is treated boiler water. A non-toxic substance is any substance that may
create a non-health hazard, is a nuisance or is aesthetically objectionable, i.e.,
foodstuff, such as sugar, soda pop, etc. Therefore, you must select the proper device
or assembly according to the type of connection and degree of hazard. There are five
basic products that can be used to correct cross-connection.
20. What are the five basic products used for protection of cross‐connections?
The five basic products are:
1. Air Gap
2. Atmospheric Vacuum Breakers ‐which also includes hose connection vacuum
breakers
3. Pressure Vacuum Breakers
4. Double Check Valve Assembly
5. Reduced Pressure Principle Backflow Preventers
21. What is an Air Gap and where is it used?
Air Gap is the physical separation of the potable and non potable system by an air
space. The vertical distance between the supply pipe and the flood level rim should
be two times the diameter of the supply pipe, but never less than 1". The air gap can
be used on a direct or inlet connection and for all toxic substances.
Because today’s complex plumbing systems normally require continuous pressure, air
gap applications are actually in the minority. It should be remembered, however, that
whenever a piping terminates a suitable distance above a contaminant, this itself is
actually an air gap. Air Gaps are frequently used on industrial processing
applications, but care should be taken that subsequent alterations are not made to the
piping, which would result in a direct connection.
22. Where is an Atmospheric Vacuum Breaker used?
Atmospheric Vacuum Breakers may be used only on connections to a non-potable
system where the vacuum breaker is never subjected to backpressure and is installed
on the discharge side of the last control valve. It must be installed above the usage
point. It cannot be used under continuous pressure.
23. Where is a Hose Bibb Vacuum Breaker used?
Hose Bibb Vacuum Breakers are small inexpensive devices with hose connections,
which are simply attached to sill cocks and threaded faucets or wherever there is a
possibility of a hose being attached which could be introduced to a contaminant.
However, like the Atmospheric Vacuum Breaker they should not be used under
continuous pressure. Remember, no shut-off valves are permitted downstream!
24. Where is a Pressure Vacuum Breaker used?
Pressure Vacuum Breakers may be used as protection for connections to all types of
non-potable systems where the vacuum breakers are not subject to backpressure.
These units may be used under continuous supply pressure. They must be installed
above the usage point. (Spill resistant models for indoor use are also available).
25. Where is a Backflow Preventer with Intermediate Atmospheric vent used?
These devices are made for 1/2" and 3/4" lines feeding residential boilers. In addition,
they provide the added advantage of providing protection against backpressure in low
hazard applications.
26. Where is a Double Check Valve Assembly used?
A double check valve assembly may be used as protection of all direct connections
through which foreign material might enter the potable system in concentration,
which would constitute a nuisance, or be aesthetically objectionable, such as air,
steam, food, or other material which does not constitute a health hazard.
27. Where is a Reduced Pressure Zone Backflow Preventer used?
Reduced Pressure Principle Assemblies may be used on all direct connections which
may be subject to backpressure or back siphonage, and where there is the possibility
of contamination by the material that does constitute a potential health hazard.
28. Are there any regulations in OSHA regarding cross‐connections?
Yes, OSHA requires that no cross-connection be allowed in an installation unless it is
properly protected with an approved backflow preventer.
These requirements are also covered in B.O.C.A., Southern Standard Building Code, Uniform Plumbing Code, IOC, UPC, and City, State and Federal Regulations.
29. What Standards are available governing the manufacture of backflow
prevention assemblies?
Reduced Pressure Backflow Prevention Assemblies, Double Check Valve
Assemblies, Pressure Vacuum Breakers and Atmospheric Breakers are specified by
USC Foundation for Cross-connection Control, ANSI/AWWA and ASSE. Dual
Check Valves and Hose Bibbs are specified by the ASSE Standards. Various
manufactures carry backflow prevention devices meeting these standards, including
Cla-Val, Febco, Hersey, Watts and Ames.
30. What is the benefit of a strainer preceding a backflow preventer?
A strainer will protect the check valves of a backflow preventer from fouling due to
foreign matter and debris, which may be flowing through the line. This not only
protects the valve but also eliminates nuisance fouling and subsequent maintenance
and shutdown. The use of a strainer with a water pressure reducing valve has been an
accepted practice for years. The amount of pressure drop attributed to the strainer is
negligible and is far outweighed by the advantages provided by the strainer.
31. What would cause a reduced pressure backflow preventer to leak?
Leakage from a backflow preventer is normally attributed to foreign matter lodging
on the seating area of either the first or second check valve. Most times this can be
corrected by simply flushing the valve, which will dislodge any loose particles. It is,
therefore, most important on new installations that the piping be thoroughly flushed
before installing the unit. It should be remembered, however, that spillage does
provide a “warning signal” that the valve is in need of maintenance.
32. Is periodic testing required for reduced pressure backflow preventers?
Yes, and this is to ensure that the valve is working properly and is a requirement of
many states and cross-connection control programs. Test cocks are provided on the
valve for this purpose and manufacturers are required to furnish field testing
information.
33. Should a backflow preventer be installed in the water supply line to each
residence?
Because of the growing number of serious residential backflow cases, many water
purveyors are now requiring the installation of approved dual check valve backflow
preventers at residential water meters. They are also educating the public concerning
cross-connections and the danger of backflow into the local water supply. Since water
purveyors cannot possibly be responsible for or monitor the use of water within a
residence, the requirements for these cross-connection control programs are
increasing throughout the country.
34. What is a cross‐connection control program?
This is a combined cooperative effort between plumbing and health officials,
waterworks companies, property owners and certified testers to establish and
administer guidelines for controlling cross-connections and implementing means to
ensure their enforcement so that the public potable water supply will be protected
both in the city main and within buildings. The elements of a program define the type
of protection required and responsibility for the administration and enforcement.
Other elements ensure continuing education programs.
35. What are the concerns with thermal expansion and backflow prevention?
Since backflow prevention devices prevent the exchange of water between the
customer and the public water provider that prevents thermal expansion, a pressure
blow-off valve must be provided at the hot water tank. Blow-off water should be
directed to a proper drain. Gas fired hot water tanks have a tendency to build
pressures quickly and these pressures can rupture internal plumbing. Customers are
advised to contact a local plumber to correct these situations.
36. What are the concerns with freezing and backflow prevention?
When temperatures are expected to fall below 32° F for several hours, standing water
in unprotected backflow prevention devices can freeze and cause the device to
rupture. Above ground non-protected backflow prevention devices should be wrapped
in insulating material and/or covered to prevent freezing. Water that is kept in motion
(by running the water continuously) will not freeze but this solution can be costly.